113841 Manual motor protective circuit breaker Ex9S80A 40BM

Novi proizvod

EAN: 8592765138415

Manual motor protective circuit breakers Ex9S80A provide overload, short-circuit and phase-failure protection for the three-phase asynchronous motors with not frequent starting. They are also suitable for power distribution line protection or can be used simply as an isolator. The right setting of adjustable overload current allows to optimize motor protection by means of circuit breaker. In case of 3P application, correct setting of Ir provides also protection against overload caused due to a phase lost. Ambient temperature compensation function reduces the impact of ambient temperature. Release testing mechanism enables to test the function of the system and control rotary knob lock mechanism prevents illegal operation. Motor protective circuit breakers can be combined with wide range of accessories including auxiliary and signal contacts, shunt trip and undervoltage releases. It is possible to create diverse combination of accessories.

Karakteristike

Parametar Vrednost
Type of control element Turn button
Rated operating voltage
With integrated auxiliary switch NO
Adjustment range undelayed short-circuit release
Phase failure sensitive YES
Rated operation power at AC-3, 230 V 11
Type of electrical connection of main circuit Frame clamp
Rated short-circuit breaking capacity Icu at 400 V, AC 50
Overload release current setting
Switch off technique Magnetic
Rated permanent current Iu 40
Height 140
Width 55
Device construction Complete device in housing
With integrated under voltage release NO
Depth 137
Rated operation power at AC-3, 400 V 18.5
Thermal protection NO
Degree of protection (IP) IP20
Number of poles 3

Dokumenta

Vrsta dokumenta Ime dokumenta Veličina Format
Návod Montážny návod Ex9S80 1.3mb PDF
Declaratie de conformitate Declaratie de conformitate Ex9S80 0.5mb PDF
Date tehnice Date tehnice Ex9S80 1.4mb PDF
Catalog Dispozitive industriale 0.2gb PDF WEB